Convert kilovolt-amperes to current in amps for single-phase and three-phase systems.

If you work with generators, motors, or distribution panels, you have probably stared at a kVA rating and wondered how many amps it actually represents. Kilovolt-amperes describe apparent power, but almost everything you buy or install — breakers, cables, contactors, transfer switches — is rated in amps. This calculator closes that gap in seconds: type in the kVA rating and the system voltage, pick single-phase or three-phase, and it tells you the exact current. It is built with generator and industrial sizing in mind, so the three-phase math that trips most people up is handled for you automatically.

What This Calculator Does

This tool converts apparent power, measured in kilovolt-amperes (kVA), into electrical current, measured in amperes (A). It handles the two system types you will meet in the real world: single-phase supplies, common in homes and small workshops, and three-phase supplies, the standard for generators, factories, farms, and commercial buildings.

For single-phase systems it divides the total volt-amperes by the voltage. For three-phase systems it applies the extra square-root-of-three factor that comes from power being shared across three conductors. You do not need to remember either formula — the calculator picks the right one from your selection and shows the arithmetic it used, so you can double-check every step.

How to Use This Calculator

Start with the kVA rating. On a generator this is printed on the nameplate, often as something like “45 kVA standby” or “100 kVA prime”. On a transformer or UPS, look for the kVA figure on the specification label. Type that number into the first field.

Next, enter the line voltage of your system. For three-phase equipment this is the voltage measured between any two phases — 400 volts in much of the world, 480 volts in North American industry, 208 volts in many commercial buildings. For single-phase it is the supply voltage, such as 230 volts or 120 volts.

Choose the system type from the dropdown, then press Calculate Amps. The result appears in a green box showing the current rounded to two decimals, plus the full formula with your numbers filled in. If you typed something impossible, like zero or a negative number, a red message explains what to fix instead of giving you a nonsense answer.

The Formulas Behind the Conversion

Apparent power in volt-amperes equals voltage multiplied by current. Since one kVA is one thousand volt-amperes, the single-phase formula is simple: current in amps equals kVA times 1000, divided by voltage. Written out: I = (kVA × 1000) ÷ V.

Three-phase power is spread across three conductors, and the geometry of three-phase systems introduces a factor of the square root of 3, about 1.732. So the three-phase formula is: I = (kVA × 1000) ÷ (V × 1.732). This is the step people most often forget, and forgetting it makes your answer wrong by a factor of 1.732 — enough to dangerously undersize a breaker.

Note that these formulas use apparent power (kVA), not real power (kW). Real power brings in the power factor, which depends on the type of load. For sizing conductors, breakers, and generator capacity, apparent power is the correct starting point because cables and breakers must carry the total current, including the reactive part.

Worked Examples With Full Arithmetic

Example 1 — a 45 kVA three-phase generator running at 400 volts. This is the classic small industrial genset, and the numbers work out like this. First multiply kVA by 1000: 45 × 1000 = 45,000 volt-amperes. Then compute the denominator: 400 × 1.732 = 692.8. Finally divide: 45,000 ÷ 692.8 = 64.95 amps. So a 45 kVA generator at 400 V three-phase delivers about 64.95 amps per phase. Try it in the calculator and you will get the same figure.

Example 2 — a 5 kVA single-phase inverter at 230 volts, typical of a home backup system. Multiply 5 × 1000 = 5,000 volt-amperes. Divide by the voltage: 5,000 ÷ 230 = 21.74 amps. A single-phase load of 5 kVA on a 230 V supply therefore draws about 21.74 amps, which tells you a 25-amp breaker and appropriately rated cable are the sensible minimum.

Example 3 — a 100 kVA three-phase transformer at 480 volts, a common North American industrial setup. Step one: 100 × 1000 = 100,000 volt-amperes. Step two: 480 × 1.732 = 831.36. Step three: 100,000 ÷ 831.36 = 120.28 amps. The full-load current is about 120.28 amps per phase, the number you would use when specifying the main breaker for that transformer.

Example 4 — a 20 kVA three-phase supply at 208 volts, as found in many commercial buildings. First: 20 × 1000 = 20,000 volt-amperes. Then: 208 × 1.732 = 360.26. Finally: 20,000 ÷ 360.26 = 55.51 amps. Notice how the lower voltage pushes the current up — the same 20 kVA at 400 volts would only be about 28.87 amps. Lower voltage always means higher current for the same power, which is why cable sizes grow as voltage drops.

How to Interpret Your Result

The number the calculator gives you is the full-load current: the amps flowing when the equipment is delivering its entire kVA rating. In practice you rarely run anything at 100 percent all day, but every protective device and conductor must be able to handle this figure safely.

Use the result as the starting point for selecting a circuit breaker. Breakers come in standard sizes, so you round up to the next available size — but for loads that run continuously (three hours or more), electrical codes generally require the breaker and conductors to be rated at 125 percent of the continuous current. A 64.95-amp generator output, for example, points to an 80-amp breaker for continuous duty.

The same current tells you how heavily a generator is loaded. If your connected load draws 40 amps from a machine rated at 64.95 amps, you are at roughly 62 percent loading — a comfortable zone where diesel generators run efficiently and last longer. Consistently running below 30 percent, on the other hand, can cause wet-stacking in diesel engines.

Sizing Breakers and Cables From Your Answer

Once you know the amps, cable selection follows from standard current-carrying-capacity tables, adjusted for how the cable is installed. A cable buried in a hot conduit carries less current safely than the same cable clipped to a cool wall, so always check the derating factors for your installation method and ambient temperature.

For motor loads, remember that motors draw a large inrush current at startup — often six times the running current. The running current from this calculator sizes the cable, but the breaker needs a motor-rated characteristic (such as a D-curve breaker) so it does not trip every time the motor starts.

On generator installations, the transfer switch and the feeder from the generator to the main panel must both be rated for at least the generator’s full-load current. Undersizing any link in that chain creates a bottleneck that can overheat long before the generator itself is in trouble.

Common Mistakes to Avoid

The most frequent error is using phase voltage instead of line voltage in the three-phase formula. On a 400 V three-phase system, the voltage between one phase and neutral is 230 V — but the formula needs the 400 V line-to-line figure. Entering 230 V instead of 400 V inflates your answer by a factor of 1.732.

The second classic mistake is forgetting the square root of 3 entirely and applying the single-phase formula to a three-phase system. Your current comes out 73 percent too high, which leads to oversized, overpriced equipment. Selecting the correct system type in the calculator prevents this completely.

A third pitfall is mixing up kVA and kW. If your equipment is rated in kilowatts, you cannot plug that number into a kVA-to-amps formula without dividing by the power factor first. A 36 kW load at 0.8 power factor is 45 kVA — using 36 in the kVA field would undersize everything downstream by 20 percent.

Finally, do not confuse the generator’s standby rating with its prime rating. Standby ratings allow no overload and assume limited running hours; prime ratings assume continuous operation. Size your breakers and cables for the rating that matches how you will actually run the machine.

Frequently Asked Questions

1. What is the formula to convert kVA to amps?

For single-phase systems, amps equal kVA times 1000 divided by voltage: I = (kVA × 1000) ÷ V. For three-phase systems, you also divide by the square root of 3: I = (kVA × 1000) ÷ (V × 1.732). The calculator above applies the correct version automatically once you choose the system type.

2. Why does the three-phase formula include the square root of 3?

In a three-phase system, power flows through three conductors whose voltage waveforms are 120 degrees apart. The total three-phase power equals the square root of 3 times the line voltage times the line current. Rearranging that relationship to solve for current is where the 1.732 factor comes from.

3. How many amps is a 45 kVA generator at 400 volts three-phase?

About 64.95 amps per phase. The math: 45 × 1000 = 45,000 volt-amperes; 400 × 1.732 = 692.8; 45,000 ÷ 692.8 = 64.95 amps. This is one of the most common generator sizes for small factories, farms, and commercial backup power.

4. Can I use this calculator for single-phase home backup systems?

Yes. Select single phase, enter the inverter or generator kVA rating and your supply voltage (for example 230 V or 120 V), and you get the current the system can deliver. A 5 kVA unit at 230 V gives about 21.74 amps, which helps you choose the right inlet breaker and cable.

5. Should I enter line voltage or phase voltage?

Always enter the line-to-line voltage for three-phase systems — 400 V, 480 V, or 208 V, not the 230 V or 120 V measured from one phase to neutral. The three-phase formula is built around line voltage, so entering phase voltage will give you an answer that is wrong by a factor of 1.732.

6. What is the difference between kVA and kW?

kVA is apparent power — the total power flowing, including the reactive component. kW is real power — the portion that actually does useful work. They are linked by the power factor: kW = kVA × power factor. Cables and breakers must handle the full kVA current, which is why generator ratings use kVA.

7. How do I size a circuit breaker from the calculated amps?

Round up to the next standard breaker size. For loads running three hours or more (continuous loads), codes typically require the breaker to be rated at 125 percent of the load current. A calculated 64.95 amps therefore calls for an 80-amp breaker on continuous duty.

8. Does power factor change the kVA to amps result?

No. The kVA-to-amps conversion uses apparent power directly, so power factor does not enter the formula. Power factor only matters when you start from kilowatts and need to convert to kVA first (kVA = kW ÷ power factor) before finding the current.

9. How many amps is 100 kVA at 480 volts three-phase?

About 120.28 amps per phase. The steps: 100 × 1000 = 100,000 volt-amperes; 480 × 1.732 = 831.36; 100,000 ÷ 831.36 = 120.28 amps. This is the full-load current you would use to specify the main breaker on a 100 kVA transformer or generator.

10. Why is the current higher at lower voltages for the same kVA?

Because power equals voltage times current, a fixed amount of power needs more current when the voltage is lower. That is why a 20 kVA load draws about 55.51 amps at 208 V but only about 28.87 amps at 400 V — and why low-voltage installations need thicker cables.

11. Can this calculator be used for motors?

It gives you the motor’s full-load running current if you know the motor’s kVA (or convert its kW rating using the power factor). For cable sizing that is exactly what you need. For breaker selection, choose a motor-rated breaker, because startup inrush current is far higher than the running current shown here.

12. What does per-phase current mean on a three-phase result?

In a balanced three-phase system each of the three conductors carries the same current, so the calculator’s answer is the current in every phase conductor. Size each phase conductor and each pole of the breaker for that figure — you do not divide it by three.

13. Is the result the same for star and delta connections?

Yes, as long as you enter the line voltage. The formula I = (kVA × 1000) ÷ (V × 1.732) uses line voltage and line current, which are the same quantities whether the load or source is connected in star or delta. The internal phase currents differ, but the line current does not.

14. How accurate is this calculator?

The math is exact for ideal balanced systems, and results are shown to two decimal places. Real installations have small imbalances between phases and voltage drops along cables, so treat the answer as the design value and apply the usual safety margins when selecting equipment.

15. Can I convert amps back to kVA?

Yes, just reverse the formula. For single-phase: kVA = (amps × volts) ÷ 1000. For three-phase: kVA = (amps × volts × 1.732) ÷ 1000. For example, 64.95 amps at 400 V three-phase gives (64.95 × 400 × 1.732) ÷ 1000 = 45 kVA, which brings you full circle.

Final Thoughts

Converting kVA to amps is one of those small calculations that sits behind almost every electrical sizing decision, from choosing a generator breaker to checking whether a feeder cable is big enough. Get the formula right — especially the square root of 3 on three-phase systems — and the rest of the design falls into place. Bookmark this calculator for the next time a nameplate gives you kVA and your shopping list needs amps.